ZENITH 140 INSTRUCTION MANUAL
106
P373, 376, 379, 382, 385, 388, 391 Function
This parameter will set the function of the digital Input.
1 = Device Fail
(Default Input 1 to 6)
Digital input is used to Fail, (put out of service), a
device connected to the relay specified in P374,
377, 380, 383, 386, 389, 392 Assignment
Digital input is used to select the device, (pump),
connected to the relay specified in P374, 377,
380, 383, 386, 389, 392 Assignment as the
current duty device (pump).
Digital input is used to provide a signal to activate
an Override “ON” condition of pumps as
determined by P302 Override Delay, P303 Min.
Override and P306 Override Level.
Digital input is used to provide a signal to activate
an Override “OFF” condition of pumps after the
expiry of the delay time as determined by P302
Override Delay.
5 = Reset.
Digital Input 7 only.
(Default Input 7)
Input is used to Reset all Device Fail conditions.
Alternatively, the +/- key can be used, whilst in
RUN, to Reset any Device Fail.
P373, 376, 379, 382, 385, 388, 391 Function
This parameter will set the function of the digital Input.
Digital Input is not assigned to any relay
Digital input is assigned to Device connected to Relay 1.
Digital input is assigned to Device connected to Relay 2.
Digital input is assigned to Device connected to Relay 3.
Digital input is assigned to Device connected to Relay 4.
Digital input is assigned to Device connected to Relay 5.
Digital input is assigned to Device connected to Relay 6.
Digital input is assigned to All relays with a device
connected.