ZENITH 140 INSTRUCTION MANUAL 
 
94 
Pump “Advanced” Parameters 
The following parameters are used to set the “Advanced” Pump features.  
Pump Run On 
This feature is used to periodically allow the pumps to continue operating 
below their normal “OFF” point, to discharge any sediment that may have 
settled at the bottom of the vessel. 
P349 Prime Level 
Sets the required level to ensure pumps are fully primed after a pump run 
on has occurred. Following a pump run on, any pump, whose “ON” point is 
below the Prime Level will be held “OFF” until the Prime Level has been 
exceeded. 
P350 Run Interval 
Set required time period, in hours, at which pump run on should occur. 
P351 Run Duration 
This parameter sets the length of time, in seconds, that pumps will run on 
for, it should be noted that only one run on is allowed per Run Interval. 
Starting 
This feature is used to reduce the effects of power surges, caused by 
switching of pumps, in the following instances, (P352) Power surge (mains 
or hydraulic) that is generated when multiple pumps are started 
simultaneously, (P353) Power resumption following a power failure.  
P352 Start Delay 
Set the required time period, in seconds, that should elapse between pumps 
starting. Default = 10 seconds. 
P353 Power Delay 
Set the required time period, in seconds, that should elapse before pumps 
are allowed to start following a power failure. Default = 10 seconds.