33 
 
Test Mode 
Test mode is used to simulate the application and confirm that all 
parameters and relay setpoints have been entered as expected. During 
simulation, there is a choice of whether the relays will change state (hard 
simulation) or not (soft simulation), but the LED’s will always change colour 
as programmed, and the mA output will change in accordance to the chosen 
mode of operation. If you wish to test the logic of the system that the relays 
are connected to then select hard simulation, but if you do not wish to 
change the relay state, then select a soft simulation. 
There are two simulation modes, automatic and manual. Automatic 
simulation will move the level up and down between empty level or the pre-
determined Start Level (P983) and Pump/Control relay switch points, if you 
wish to change the direction of the level movement e.g. to go beyond relay 
setpoints, this can be done by using the arrow keys. In manual simulation, 
using the arrow keys will allow you to move the level up and down as 
required. 
To enter simulation, first go to program mode. Using the menu system, 
select menu item ‘Test’, then sub-menu item ‘Simulation’. Simply change 
the value of the parameter P980 to one of the following: 
1= Manual soft simulation   
2= Automatic soft simulation   
3= Manual hard simulation   
4= Automatic hard simulation 
To return to program mode, press ‘CANCEL’ and test mode will end. 
When in manual simulation, by default test mode will move the level by 
0.1m steps. Altering the increment (P981) will change this value. 
In automatic mode, the rate at which the level moves up and down is set by 
the increment (P981 in metres, and the rate (P982) in minutes, which can be 
changed to make the level move up and down faster. E.g. if increment 
(P981) is set for 0.1m and rate (P982) is set to 1 min then the level will 
increase or decrease at a rate of 0.1m/min. To make the simulated level 
move slower, decrease the value in increment (P981) or increase the value 
in rate (P982). To make the simulated level move faster, increase the value in 
increment (P981) or decrease the value in rate (P982).