Float Switch (FS) Backup 
About Float Switch Backup 
This digital feature is used with a float switch, where it can be used alongside 
a transducer or as a backup method for when a transducer goes into failsafe.   
The high input will have a timer and a level set point, which will allow for the 
unit to power on every pump below the set point for the specified amount 
of time as set in P332 Pump Run Time.   
The low input will simply switch off all the pumps that have been set on the 
controller. 
Common Par 
P330 Mode of Operation 
Float Switch Backup is not used 
Backup will be active continuously and will always 
respond to an input from a Backup device, always. 
Backup will only be active at times when the unit 
has gone into a Failsafe mode. 
 
P330 Input Filter 
This parameter can be used to ignore spurious changes of state on the 
digital inputs and determines the time that a change of state must be 
present before it is recognised as a valid input. 
Enter a value in seconds: Min = 1 (Default), Max = 999. 
P330 Pump Run Time 
This parameter tells the unit to switch the pumps off after the specified 
amount of time, if the level of the float switch has not been reached. 
Enter a value in minutes:  Min = 0.1 (Default), Max = 9999.