mA Limits 
P836 mA Low Limit 
This parameter sets the lowest level that the mA output will drop to, the 
default is 0mA, but you can override this if the device you connect to cannot 
for example accept less than 2mA, yet you want to use the 0-20mA range. 
Default = 0.00mA 
P837 mA High Limit 
This parameter sets the highest level that the mA output will rise to, the 
default is 20 mA, but you can override this if the device you connect to 
cannot for example accept more than 18 mA, yet you want to use the 0-20 
mA range. Default = 20.00mA 
mA Trim 
P838 mA Low Trim 
If the device you are connected to is not calibrated, and not showing the 
correct low value (reading), then you can trim it using this parameter. You 
can either type in the offset directly or use the arrow keys to move the 
output up and down until you get the expected result (reading) on the 
device that is connected. 
P839 mA 1 High Trim 
If the device you are connected to is not calibrated, and not showing the 
correct high value (reading), then you can trim it using this parameter. You 
can either type in the offset directly or use the arrow keys to move the 
output up and down until you get the expected result (reading) on the 
device that is connected.