PULSAR MEASUREMENT
47
To program the Zenith 140 for Example 2 Sump control (pump down) by
using the Quick Setup menu proceed as follows. If required to access
Program Mode, key in the passcode 1997 and press ENTER
At the Quick Setup menu press ENTER and as prompted, by the questions,
select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump
Up/Down/Differential
2 = Pump Down
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 1
Pump No. 2
2 = Set to relay 2
Type Alarm 1
1 = High Alarm
Alarm No. 1
5 = Set to relay 5
Xducer (P101)
2 = dB6
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run
mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Zenith 140 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options
Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either
by the main menu system or directly via parameter number and changed
as necessary.