Relay will energise “ON” when Flush condition is in effect 
and goes off when Flush condition is cleared. A relay being 
used for Flush Valve/Pump must be assigned to one of the 
main pumps in use. Flush relay Alarm ID (P212, 222, 232, 
242, 252, 262) is used to enter the relay number, to which 
the assigned pump is connected.  
Flush Valve/Pump relay requires three setpoints. The first set 
point (P213, 223, 233, 243, 253, 263) determines the Flush 
Interval, which is the number of main pump cycles that 
should occur before the Flush Valve/Pump operates. The 
second setpoint (P214, 224, 234, 244, 254, 264), sets the 
number of Flush cycles the Flush Valve/Pump will operate 
for. This means that the Flush Valve will be operated for 
several main pump starts (Flush Cycles) after which the Flush 
Valve activity will cease until the Flush Interval comes 
around again.   Setpoint three of the Flush Valve/Pump relay 
sets the Flush Duration, (P215, 225, 235, 245, 235, 236) this 
is the duration for Flush 
Step Time Control allows relays to be used to control a 
device, such as a motorised valve or gate, in order to 
maintain the level within two predetermined points. Relays 
will energise “ON” when Step Time condition is in effect and 
de-energises “OFF” when Step Time goes off. One relay will 
be required to control an increase in level, (‘open’ the device) 
and a second relay is required to control a decrease in level, 
(‘close’ the device). Alarm ID (P212, 222, 232, 242, 252, 262) 
is used to assign the relay to control either the open or close 
condition. Step Time Control relay requires three setpoints. 
The first set point (P213, 223, 233, 243, 253, 263) determines 
the level, at which the relay is to be activated, (N.B. level 
setpoint for open relay, increase the level, must be lower 
than the setpoint for the close relay, decrease the level). The 
relay will energise “ON” after the Limit time that is set in 
Relay Setpoint 3 (P215, 225, 235, 245, 255, 265). And turns 
“OFF”, de-energises, after the Drive Period that is set in 
Relay Setpoint 2 (P214, 224, 234, 244, 254, 264).