EasyManuals Logo

Quantech QTC3040T User Manual

Quantech QTC3040T
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #194 background imageLoading...
Page #194 background image
Quantech
194
Form QTC3-NM1
Issue date: 12/19/2023
Section 9: Service and troubleshooting
Problem Cause Solution
Low liquid temp fault
1. Improperly adjusted leaving
chilled liquid temp. cutout (glycol
only).
1. Re-program the leaving chilled liquid temp.
cutout.
2. Micro panel setpoint/range
values improperly programmed.
2. Re-adjust setpoint/range.
3. Chilled liquid ow too low.
3. Increase chilled liquid ow. See Operational
limitations on page 47).
4. Defective LWT or RWT sensor
(ensure the sensor is properly
installed in the bottom of the well
with a generous amount of heat)
conductive compound).
4. Compare sensor against a known good
Temperature sensing device. See Table 32
on page 186.
Mp / hpco fault
1. Compressor internal motor
protector (MP) open.
1. Verify refrigerant charge is not low. Verify
superheat setting of 10°F to 15°F (5.6°C to
8.3°C). Verify correct compressor rotation.
Verify compressor is not overloaded.
2. External overload tripped. 2. Determine cause and reset.
3. HPCO switch open. 3. See High Press. Disch. Fault.
4. Defective HPCO switch. 4. Replace HPCO switch.
5. Defective CR relay. 5. Replace relay.
Compressor(s) won’t start
1. Demand not great enough. 1. No problem. Consult Installation Manual to
aid in understanding compressor operation
and capacity control.
2. Defective water temperature
sensor.
2. Compare the display with a thermometer.
Should be within plus or minus 2 degrees.
See Table 32 on page 186 for RWT/LWT
temp./voltage table.
3. Contactor/Overload failure. 3. Replace defective part.
4. Compressor failure. 4. Diagnose cause of failure and replace.
Lack of cooling e󰀨ect
1. Fouled evaporator surface.
Low suction pressure will be
observed.
1. Contact the local Quantech service
representative.
2. Improper ow through the
evaporator.
2. Reduce ow to within chiller design specs.
See Operational limitations on page 47).
3. Low refrigerant charge. Low
suction pressure will be
observed.
3. Check subcooling and add charge as
needed.
Table 35: Troubleshooting, continued

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Quantech QTC3040T and is the answer not in the manual?

Quantech QTC3040T Specifications

General IconGeneral
BrandQuantech
ModelQTC3040T
CategoryChiller
LanguageEnglish

Related product manuals