Quantech
69
Section 5: Technical data
Form QTC3-NM1
Issue date: 12/19/2023
55
Table 12: Electrical data without pumps, R-454B, continued
QTC3 V Hz MCA Min. N/F
disc SW
Min. dual
elem. fuse
and CB
Max. dual
elem. CB
System 2
Compr. 1 Compr. 2 Compr. 3 Std. ow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
3205T
208 60 734 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.6 44
230 60 731 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.4 37
380 60 443 600 500 500 62.2 355 62.2 355 62.2 355 6 4.5 23.1
460 60 369 600 400 400 51.4 316 51.4 316 51.4 316 6 4 19
575 60 292 400 300 300 41.1 258 41.1 258 41.1 258 6 2.9 15.3
3225T
208 60 904 1,200 1,000 1,000 130.1 761 130.1 761 130.1 761 6 7.6 44
230 60 902 1,200 1,000 1,000 130.1 761 130.1 761 130.1 761 6 7.4 37
380 60 498 600 500 500 71.1 475 71.1 475 71.1 475 6 4.5 23.1
460 60 472 600 500 500 67.9 344 67.9 344 67.9 344 6 4 19
575 60 339 400 350 350 48.7 296 48.7 296 48.7 296 6 2.9 15.3