Manual DFA 127 Full Power 12/2006 Rev. B Page 31 of 55
Configuration
Parameter Setting
range
Factory
default
Description
Standard
arm
Standard arm for pushing opening
Sliding
pulling
Sliding arm for pulling opening
Sliding
pushing
Sliding arm for pushing opening
Types of arms
Inheader
Sliding pull-
ing
Special application (for USA only)
Disabled Inverse
Enabled
Enabled Opening of the door by spring ten-
sion in case of power failure.
Spring type Display
only
EN 4 Springiness value is estimated dur-
ing calibration run (MF 6. light pulse).
Control with FPC 902:
Spring type: EN 4: value from 35-41
Display Unknown, if the value could
not be estimated or lies out of range.
Disabled Limit open
Enabled
Disabled Enabled: The door is hold stronger in
the open position.
ENTRANCE SYS-
TEM
Disabled Fire alarm
Enabled
Enabled Enabled: specific adaptation for the
requirement of the EN-norms for fire
doors.
Single
control
Master
control
Control
Slave
control
Single
control
This setting is effected automatically
under operating conditions. Simula-
tion or Master/Slave-Control can be
set with the FPC 902.
Interlock type Without
interlock
Without
interlock
Function not yet integrated
Basic
operator
USA
USA Low
Energy
UK
Door type
UK Low
Energy
Basic
operator
Frequently-used door types can be
chosen for specific applications.