Mosaic fieldbus modules
8540801 • 01/02/2017 • Rev.15 13
LED NET
STATE
STATE
OFF
No power or no IP address
GREEN
On-line, connected
GREEN blinking
On-line, not connected
RED
Duplicate IP address
RED blinking
Connection timeout
LED STS
STATE
STATE
STATE
OFF
No power
-
GREEN
RUN state
-
GREEN blinking
Not configured
-
RED
Fatal error
One or more non-recoverable errors detected
RED blinking
Error
One or more recoverable errors detected
LED NET
STATE
INDICATES
DESCRIPTION
OFF
Offline
No power
Connection with IO controller not present
GREEN
Online (Run)
Established connection with IO controller
IO controller in RUN state
GREEN blinking
Online (Stop)
Established connection with IO Controller
IO Controller in STOP state
LED STS
STATE
INDICATES
DESCRIPTION
OFF
Not initialized
No power or Module in SETUP or NW_INIT state
GREEN
Normal operation
Module has shifted from the NW_INIT state
GREEN blinking (1 flash)
Diagnostic event (s)
Diagnostic event (s) present
GREEN blinking (2 flashes)
Blink
Used to identify the network node
RED
Exception
Module in EXCEPTION state
RED blinking (1 flash)
Configuration error
Identification error
RED blinking (2 flashes)
IP address error
IP address not configured
RED blinking (3 flash)
Station name error
Station name not configured
RED blinking (4 flashes)
Internal error
Module has encountered a major internal error