Mosaic fieldbus modules
8540801 • 01/02/2017 • Rev.15 16
FAULT DIAGNOSIS
MEANING
LED
ON
RUN
IN FAIL
EXT FAIL
LED1
LED2
GREEN
GREEN
RED
RED
RED/GREEN
RED/GREEN
Internal fault microcontroller
ON
OFF
2 flashes*
OFF
see the modules tables
Internal board fault
ON
OFF
3 flashes*
OFF
Configurazione Error
ON
OFF
5 flashes*
OFF
BUS communication Error
ON
OFF
5 flashes*
OFF
BUS communication interruption
ON
OFF
ON
OFF
Detected an identical module
ON
OFF
5 flashes*
5 flashes
* The LED frequency of flashing is: ON for 300ms and OFF for 400ms, with an interval between two sequences of 1s.
Example 1
In the example shown in Figure 4, Input 1 (connected to module M1) is tested with the M1-T1
test signal. During wiring, the 24Vdc is connected to input 1 instead of the M1-T1 test signal.
-
The I/O index and Diagnostic code fields assume the following values: 1 - 20 to
indicate the diagnostics on input 1 of module M1 (Connection error).
Figure 4
Example 2
In this example, the I/O index corresponds to the logical block and not to the physical terminal
on module M1.
In Figure 5 for example, the two-hand element connected to the Input 1 and Input 2 physical
terminals corresponds to I/O index No. 1 and the emergency stop connected to the Input 3 and
Input 4 terminals corresponds to I/O index No. 2.
Figure 5