8540801 • 01/02/2017 • Rev.15 15
DB9 female
(front view)
Pin
Direction
Signal
Description
Housing
-
PE
Protective Earth
1
-
GND
Bus polarization 0VDC (isolated)
2
OUT
5V
Bus polarization +5VDC (isolated)
3
IN
PMC
Connect to pin 2 for RS-232 / Leave unconnected for RS-485
4
-
-
-
5
Bidirectional
B-line
RS-485 B-line
6
-
-
-
7
IN
Rx
RS-232 Data Receive
8
OUT
Tx
RS-232 Data Transmit
9
Bidirectional
A-line
RS-485 A-line
LED NET
STATE
INDICATES
DESCRIPTION
OFF
No power or no data exchange
-
YELLOW
Frame Reception or Transmission
Data exchange
RED
Fatal Error
One or more non-recoverable errors detected
LED STS
STATE
INDICATES
DESCRIPTION
OFF
Initializing or no power
-
GREEN
Module initialized
Module initialized no error
RED
Fatal Error
One or more non-recoverable errors detected
RED blinking (1 flash)
Communication fault or
configuration error
Invalid setting in Network Configuration Object
Setting in Network Configuration Object has been changed
during operation
RED blinking (2 flashes)
Application diagnostic available
-
LED CONNECT
STATE
INDICATES
DESCRIPTION
Green
USB connected
Module connected to Pc via USB
OFF
USB not connected
Module not connected