Table 2 .C
FUSE REQUIREMENTS
Dual Element Class
HP
A-C Line K5, 250 VAC Fuse
Volts Quantity Amp
FOR BASIC MOTOR PROTECTION
1/4 -7'4
115 1(D
15
1/2-11/2
230 2
15
2-3
230 2
25
5
230 2
45
le
FOR SUPERIOR MOTOR PROTECTION
1/4
115 1(D 6.25
1/3
115 1(D
10
1/2
115 1(D 10
7'4
115 1(D 15
1/2
230 2 6.25
:y4
230 2
10
1 230 2
10
11/2
230 2 15
2
230 2 20
3
230
2 25
5
230 2 45
(!) Install fuse in input line Ll (hot line ).
Table 2.D
D-C MOTOR / CONTROLLER / TRANSFORMER SPECIFICATIONS
CONTROLLER
OPTIONAL
TRANSFORMER
MODEL NUMBERS
D-C
POWER
A-C D-C ARM.
D-C AMP.
SUPPLY
MAXIMUM
FULL
AMPS
ARM.
AMPS FIELD
MAX. CAPACITY
kVA LOAD
BASIC COMPLETE
HP
VAC (RMS) (VOLTS)
(avg.) VOLTS
(optional)
CD
Per Phase
kVA
1/4
115 3.5
90
2.5
100
3.0 5000
40 0.75
14C50 14C50/ 14C80
%
115 5.2 90
3.7 100
3.0 5000
40 0.75
1/2 115 7.0 90
5.0
100
3.0 5000
40 1.0
%
115 10.5 90
7.5
100
3.0
5000
40 1.5
112 230 3.5
180
2.5 200
3.0 5000
40
1.0
14C51
14C51/ 14C81
%
230
5.2 180
3.7
200
3.0
5000
40 1.5
1 230
7.0
180 5.0
200 3.0
5000
40
2.0
11/2
230 10.5
180 7.5
200
3.0
5000
40
3.0
14C52 14C52/ 14C82
2 230
14.0 180 10.0
200 3.0(D
5000
40
5.0
3
230
21.0
180 15.0
200
3.0(D
5000
40
5.0
14C53
14C53/ 14C83 5 230
35.0 180 25.0
200
3.0(D
5000
40 10.0
CD Standard
CD Maximum permissible availabl e symm etri cal RMS fault curr ent with NEC or CEC external approved disconnect .
7