EasyManua.ls Logo

REMEHA Selecta - Page 52

REMEHA Selecta
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Remeha Selecta
52
Fig. 23 Setting screws
00.W5H.79.00005
Procedure:
- Remove the boiler front panel (see Par. 8.1).
- Set the boiler to 'Forced High' mode, (see Par. 9.2.5).
- Remove the measuring point sealing cap (in the boiler flue) and insert the combus-
tion equipment probe.
- After reaching the full load speed, allow the boiler temperature to rise and settle to
about 70
o
C, measure the O
2
/CO
2
percentage and compare it with the value in the
table. Correct, if necessary, the gas/air ratio with the aid of set screw A on the gas
block (see Fig. 23).
- Check the flame via the inspection glass, the flame must be stable with no lifting off
and the burner surface shows glowing (orange) dots.
- Set the boiler to 'Forced Low' mode, (see Par. 9.2.6).
- After reaching the part load speed, allow the boiler temperature to settle, measure
the O
2
/CO
2
percentage and compare it with the value in the table.
- Correct, if necessary, the gas/air ratio with the aid of set screw B on the gas block
(see Fig. 23).
- Check the flame via the inspection glass, the flame must be stable with no lifting off
and the burner surface showing an even, orange glow.
- After adjusting the part load settings, a check must be carried out on full load set-
ting as this can be effected by the part load adjustment. If necessary, correct the full
load setting.

Table of Contents

Related product manuals