REYMSA COOLING TOWERS, INC.
www.reymsa.com
The
All-Fiberglass
Cooling Towers
67
D. MAINTENANCE
Proper maintenance is necessary to increase the equipment’s service life. Adequate knowledge of the
operation and maintenance of REYMSA Cooling Towers is essential for efficient and safe operation.
REYMSA recommends that Inspection of the Cooling Tower should be performed yearly; appropriate
cleaning or repairs should be performed if necessary; however, it is also convenient to perform regularly a
general inspection for any unusual noises, vibration, water leakages, excessive drift and the set-up of initial
conditions, like amps and water flow (see also section “E. TROUBLE-SHOOTING”). The water quality needs
to be checked also on a regular basis.
The yearly inspection routine includes the basin, the Tower’s body (which includes the water distribution
system, the fill media and the drift eliminators) and the fan and its motor; see on Table D-1 the Maintenance
schedule recommended by REYMSA.
Operation, Maintenance and Repair of REYMSA Cooling Towers should be
done by Qualified Personnel.
WARNING
Follow maintenance guidelines as recommended by REYMSA to avoid
unnecessary equipment malfunction and assure good Cooling Tower performance.
WARNING
Do not proceed with any Inspection or Maintenance Procedure without
disconnecting and locking out Power for the Motor and Pump. Failure to do so
may result in personal injury or property damage.
WARNING
Maintenance