Explanation for 4 X register :
Address Parameter Description
40005
40007
System Voltage
This address is read only and displays System Voltage
40009
System Current
This address is read only and displays System Current
This address is used to set the System type.
Write one of the following value to this address.
1 = 1 Phase 2 Wire (Read only for 1P2W)
2 = 3 Phase 3 Wire 3 = 3 Phase 4 Wire.
Writing any other value will return error .
40011
System Type
40013
Pulse Width
of Relay
This address is used to set pulse width of the Pulse output.
Write one of the following values to this address:
60 : 60 ms
100 : 100 ms
200 : 200 ms
Writing any other value will return error .
40015
Reset
Parameters
This address is used to reset the parameters by writing following.
0 : Energy reset 2 : Sys. Min reset
3 : Sys. Max reset 6 : Reset all.
Writing any other value will return an error.
Energy display
on Modbus
This address is used to set energy display on MODBUS in Wh,
KWh & Mwh. Write one of the following value to this address.
1 = Energy in Wh. 2 = Energy in KWh.
3 = Energy in MWh.
53

Table of Contents

Other manuals for Rish Master 3430

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rish Master 3430 and is the answer not in the manual?

Rish Master 3430 Specifications

General IconGeneral
BrandRish
ModelMaster 3430
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals