EasyManuals Logo

Rish Master 3430 User Manual

Rish Master 3430
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
4. ESD precautions must be taken at all times when handling this product.
3. To protect the product against permanent damage, surge transients must be limited to
2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source.
The unit has been designed to automatically recover in the event of a high level of
transients. In extreme circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via
Current Transformers only, where one side is grounded.
8.2 Case Dimension and Panel Cut Out
3.78”
96mm
FRONT DISPLAY
AREA
3.78”
96mm
3.15”
80mm
3.62”
92mm
PANEL CUTOUT
3.62”
92mm
MAX PANEL THICKNESS 0.18”,5mm
8.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure.
Numbering is clearly marked in the plastic moulding. Choice of cable should meet local
2
regulations. Terminal for both Current and Voltage inputs will accept upto 3mm x 2
diameter cables.
Note : It is recommended to use wire with lug for connection with meter.
68

Table of Contents

Other manuals for Rish Master 3430

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rish Master 3430 and is the answer not in the manual?

Rish Master 3430 Specifications

General IconGeneral
BrandRish
ModelMaster 3430
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals