4 Operation
Manual TME400-VMF · EN02 · 2018 September 6th
60
G20
Date of last battery
replacement
Shows the date of the last battery replacement
Coor-
dinate
Name
Modbus
register
Modbus
access
Protec-
tion
Data
type
Min.
Max.
Default
Unit
G01
Current error
675
R
A
unit16
-
-
0
ERR
G02
Software version
676
R
A
float
-
-
*
Rev
G04
Serial number
680
W
E
int32
0
99999999
0l
SNo
G05
Firmware checksum
682
R
A
int16
-
-
*
CRC
G06
Measuring point
314
W
A
unit32
*
*
0
Rev
G18
Meter number
699
W
E
int32
*
*
9999
9999
MNo
G19
Meter size
701
W
E
string8
*
*
4-
16000
G
G20
Date of last battery re-
placement
705
W
C
int32
*
*
0101
2014
Bat
4.3.3.5.
RS-485 interface
Coor-
dinate
Name
Description
H01
RS-485 Baud rate
2400 Bps
9600 Bps
19200 Bps
38400 Bps (default)
H02
RS-485 parameter
0
8N1 (default)
1
8E1
2
8O1
3
7N1
4
7E1
5
7O1
H03
RS-485 protocol
0
Off
1
Modbus RTU (default)
2
Modbus ASCII
H04
Modbus ID
Modbus device address (default = 1).
H05
Modbus register offset
The offset is defined as 1 by RMG.
Coor-
dinate
Name
Modbus
register
Modbus
access
Protec-
tion
Data
type
Min.
Max.
Default
Unit
H01
RS-485 Baud rate
709
W
N
menu16
0
3
3
Bps