EasyManuals Logo

RMG TME400-VMF User Manual

RMG TME400-VMF
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
4 Operation
MANUAL TME400-VCF · EN08 · July, 01
st
2021
75
Coor-
dinate
Name
Modbus
register
Modbus
access
Protec-
tion
Data
type
Min.
Max.
Default
Unit
G01
Current error
675
R
A
uint16
-
-
0
ERR
G02
Software version
676
R
A
float
-
-
*
Rev
G04
Serial number
680
W
E
int32
0
99999999
0l
SNo
G05
Firmware checksum
682
R
A
int16
-
-
*
CRC
G06
Measuring point
314
W
A
uint32
*
*
0
Rev
G10
Standard pressure
683
R
A
float
-
-
1.0
bar
G11
Pressure range min.
685
R
A
float
-
-
0.7
bar
G12
Pressure range max.
687
R
A
float
-
-
2.0
bar
G13
Pressure sensor serial
number
689
R
A
string12
-
-
*
---
G14
Standard temperature
695
R
A
float
-
-
273.15
TN
G17
Temperature sensor se-
rial number
697
W
E
int32
*
*
9999
9999
TNo
G18
Meter number
699
W
E
int32
*
*
9999
9999
MNo
G21
CRC metrological Param.
EEprom
804
R
A
string8
-
-
CALC
Hex
G23
Date of Battery Exchange
705
W
C
string8
-
-
010117
Bat
G24
Remaining Battery Ca-
pacity
790
R
A
uint16
-
-
100
%
G25
Battery Change
791
W
C
menĂ¼16
0
1
0
-
G26
Operating Hours
792
R
A
uint32
-
-
0
h
G19
Meter size
701
W
E
string8
*
*
4-16000
G
G20
Batter replacement date
705
W
C
int32
*
*
0101
2014
Bat
4.3.3.8. RS-485 interface
Coordi-
nate
Name
Description
H01
RS-485 Baud rate
2400 Bps
9600 Bps
19200 Bps
38400 Bps (default)
H02
RS-485 parameter
0
8N1 (default)
1
8E1
2
8O1

Table of Contents