Rockwell Automation Publication 856T-UM001B-EN-P - April 2021 23
Chapter 3 Configure the 856T-B24LC IO-Link Module
4. Name the Ethernet adapter (in this example we used name PointIO), set
the chassis size, check the module revision, and configure the adapter IP
address. Click OK and Close.
5. The 1734-AENTR adapter is now visible in the Controller Organizer tree
in the Ethernet section.
Add IO-Link Master Now, the IO-Link Master module must be added. Make sure that the controller
is Offline before you start configuration.
1. In the Controller Organizer tree, find Ethernet under I/O Configuration.
Right-click the 1734-AENTR adapter and select New Module.