Rockwell Automation Publication 856T-UM001B-EN-P - April 2021 73
Appendix E
Factory Reset
Reset to Factory Settings —
Variables
Table 26 shows what 856T-B24LC module variables can be reset to factory
settings when a command (0x082) is received via the IO-link protocol.
Table 26 - Reset to Factory Settings Variables
Parameter
Name
ISDU (Hex/Dec) Access Size Data Type Storage Min Max Default
Application-
Specific Tag
0x0018/24 Read/write 256 StringT Non-volatile “”
Device Access
Locks
0x000C/12 Read/write 16 RecordT Non-volatile 0 3 0
Master Cycle
Time
0x0001/01 Read/write 8 UIntegerT Non-volatile
Alarm
Configuration
0x014E/334 Read/write 16 RecordT Non-volatile 0 4095 4095
Calibration
Status
0x0134/308 Read-only 1 UIntegerT Non-volatile 0 2 0
Circuit Counters
Enable
0x0141/321 Read/write 8 RecordT Non-volatile 0 0x7F 0
Circuit Cycle
Counter
0x0132/306 Read-only 224 RecordT Non-volatile 0 4294967296 0
.Module (Circuit_ ) 0x0133/307 Read-only 56 RecordT Non-volatile 0 7 0
Module Type 0x0138/312 Read/write 56 RecordT Non-volatile 0 11 0
Vibration
Calibration
Period
0x0144/324 Read/write 16 UIntegerT Non-volatile 0 480 10
Vibration
Warning Limit
0x0143/323 Read/write 48 RecordT Non-volatile 0 16000 16000
IMPORTANT If you want to perform the Reset to Factory Settings of the parameters
shown in Table 26
when connected to a 1734-4IOL IO-link master, you
must perform the task manually for each one of these parameters. In
some cases (such as Circuit Cycle Counter), a given ISDU may include
several subindexes that must be reset individually.