EasyManua.ls Logo

Rockwell Automation Allen-Bradley 856T-B24LC - Validation of Write; Service Code

Rockwell Automation Allen-Bradley 856T-B24LC
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 856T-UM001B-EN-P - April 2021 51
Chapter 7 Message Structure and Configuration Example
Validation of Write Once the Message Instruction dialog box has been populated; trigger the rung
of logic that contains the message instruction. The word Test is written from
the Write_Assembly to the Application-Specific Name Parameter Index in the
856T-B24LC module.
The data is validated when reading the value of Index 24 in the sensor or when
viewing the 1734-4IOL configuration. To view the configuration of the
1734-4IOL, follow these steps:
1. Click the 1734-4IOL in the IO Configuration.
2. A popup window appears and advises that changes within the
856T-B24LC module have been detected. Expand the settings and to see
that the Application-Specific Name has changed to Test.
3. Click Upload.
4. Click OK and the new parameter values are uploaded into the controller.
The new Application-Specific Name can be seen when viewing the
Identification Tab of the AOP for the 856T-B24LC module.
Service Code The following table is used to determine the Service Code that is needed for a
specific Message Instruction.
Service Code
(Hex)
Need in Implementation
Service Name Description of Service
Class Instance
4B Required Required Read Subindex
Reads a parameter value from the IO-Link
device
4C Required Write Subindex
Writes a parameter value from the IO-Link
device
4D Required Required Read Index
Reads an entire index (all parameters
within an index) from the IO-Link device
(uses subindex 0)
4E Required Write Index
Writes an entire index (all parameters
within an index) from the IO-Link device
(uses subindex 0)

Table of Contents

Related product manuals