EasyManua.ls Logo

Rockwell Automation Allen-Bradley Micro830

Rockwell Automation Allen-Bradley Micro830
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2080-UM002L-EN-E - November 2021 25
Chapter 2 About Your Controller
Insufficient Controller Memory Example
Limitations of RMC
Take note of the following limitations when using the Run Mode Change
(RMC) feature:
Configuration changes cannot be made (for example, change filter
times).
Up to 2KB of logic (approximately 150 boolean instructions) and us
er
va
riables and can be added for each Test Logic.
Total memory allocated for RMC (cumulative of all Test Logi
c Changes)
can be increased from 2KB to 8KB, but t
he 2KB limit for logic and us
er
variables per Test Logic remains.
Up to 20 POU (Program Organization
al Units) can be added for each
ch
ange (for example, if you currently have 5 POU, you can add 20 mo
re
fo
r a total of 25 POU).
If a User Defined Function Block is modified that changes the lo
cal
vari
ables, the local variables will be reinitialized or reset to
zero and a
warning message w
ill be shown during the build. If you wa
nt to reapply
the ini
tial value, right-click on the UDFB and select Refactor
Reset
Initial V
alues of Instances.
RMC is not possible after doing a Discover Project operatio
n if a new
module is detected because the configuration has
changed.
Exchange files cannot be imported when in RMC because it is considered
a configuration change.
Making changes to the display configuration (for
example, hiding
comments) are treated a
s logic changes and
require you to build the
projec
t.
Global variables cannot be deleted or modified in RMC, but can be added.
To delete or modify a global variable, Connected Comp
onents
Workbench
software must be disconnected from the controller.
W
hen using CIP™ messaging in RMC, setting the CIPTARGETCFG data
type pa
rameter ConnClose to TRUE ha
s no effect. The Ethernet session
does not close im
mediately upon succ
essful messaging and you have to
wait for th
e connection to timeout after 60 seconds. This applies
to
Connected Components Workbench softwar
e
version 9 or earlier
projects. For version 10 o
r later proj
ects, the CIP connection timeout is
configurabl
e.
See Use Run Mode Change
on page 242 for an example on how to use this
feature.
WARNING: If you delete the output rung when in Run Mode Change and accept the
changes, the output on the controller will remain ON.
Controller Memory
(for User Program + Data)
RMC Memory
(Default size = 2KB)
Error will occur due to insufficient
controller memory remaining
Free RMC memory
Used memory

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley Micro830

Related product manuals