EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerFlex 700S - Motor Overload

Rockwell Automation Allen-Bradley PowerFlex 700S
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
72 Rockwell Automation Publication 20D-PM001D-EN-P - March 2019
Chapter 2 Programming and Parameters
375 Inv OT Pend Cnfg
Enter a value to configure the drive's response to a Inverter Over-Temperature (OT) Pending exception event. This
event is triggered when the Inverter Negative Temperature Coefficient (NTC) function detects the heat-sink
temperature reaches to the overload warning level.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
1 =
0 =
1 =
2 =
3 =
4 =
“Al arm
“Ignore
“Al arm
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp
376 Inv OL Pend Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Pending exception event. This event is
triggered when one of the Inverter Protection Current-Over-Time functions (Open Loop or Closed Loop) detects
current and temperature at warning levels.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
1 =
0 =
1 =
2 =
3 =
4 =
“Al arm
“Ignore
“Al arm
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp
377 Inv OL Trip Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Trip exception event. This event is
triggered when one of the Inverter Protection Current-Over-Time functions (Open Loop or Closed Loop) detects
current and temperature at a fault level.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
Default:
Options:
1 =
0 =
1 =
2 =
“Al arm
“Ignore
“Al arm
“FltCoastStop”
378 Interp Flt Cnfg
Enter a value to configure the drive's response to a position interpolator exception event. If the interpolator loses
the synchronization pulse or is out of synch, this event occurs.
Default:
Options:
1 =
0 =
1 =
2 =
“Al arm
“Ignore 3 = “Flt RampStop”
Alarm 4 = “FltCurLimStp
“FltCoastStop”
379 Ext Flt/Alm Cnfg
Enter a value to configure the drive's response to an External Input exception event. The event is triggered by a
digital input that is configured for auxiliary fault or auxiliary aux fault by selecting 3 “Ext Fault” or 38 “ExtFault
Inv” in Par
825 [DigIn 1 Sel], Par 826 [DigIn 2 Sel] or Par 827 [DigIn 3 Sel].
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore
“Al arm
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp
381 PreChrg Err Cnfg
Enter a value to configure the drive's response to a Precharge Error exception event.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event
Default:
Options:
2 =
0 =
1 =
2 =
“Al arm
“Ignore
“Al arm
“FltCoastStop”
382 MC Cmd Lim Cnfg
Enter a value to configure the drive's response to a Motor-Controller (MC) Command Limitation exception event.
This event is triggered when the motor-controller detects limit of the command values used in the motor-
controller, and returns the exception event to the Velocity Position Loop (VPL).
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
Default:
Options:
2 =
0 =
1 =
2 =
“Al arm
“Ignore
“Al arm
“FltCoastStop”
No. Name
Description
Values
Linkable
Read-Write
Data Type

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 700S

Related product manuals