Servicing and cleaning
74 / 97
Inspection procedures
Engine coolant inspection
Remove the pressure cap from the compensation tank at room tem-
perature. The coolant should be between the MIN and MAX markings
in the compensation tank.
If necessary, fill the tank with coolant and fit the pressure cap.
Use VOLVO VCS coolant for the initial filling.
Coolants may not be mixed together.
Temperature stability control
Remove the pressure cap from the compensation tank.
With the coolant probe, check the temperature status. This should be
at least -20 °C.
Leak testing
The check for leak tightness should be done every 3 months, after a com-
plete drainage of the portable fire pump.
Drain pump carefully.
Open drain cock (J7).
Close the suction inlet (J15) with a blank cap.
When checking suction hoses, connect them to the suction inlet
and close the end with a blank cap.
Close pressure valve(s) (J10)
Actuate Priming pump function switch (S3) to activate the priming
pump.
If only the pump is checked, a vacuum of 0.8 bar is reached in a few
seconds.
The pump is tight enough, if the vacuum does not drop below 0.1 bar
within one minute.
If 0.8 bar cannot be reached, the pump should be put under pres-
sure by water induction. A pressure of 3-6 bar connected to the
suction inlet is sufficient.
The leak check is carried out.
Release vacuum after the leak check.
Briefly open the pressure outlet(s) (J10) or drainage (J7).