User Manual - 13/32
4.3 OPERATION MODE
Operation mode for the oor sensor can be set set to either “OFF”, “Floor protection” or “Comfort”. Choose wished mode using ▼ – pres MENU.
OFF this turns o the sensor completely.
Floor protection this function serves to maintain the oor temperature below the maximum temperature value in order to protect
the system or ooring against overheating. When the oor temperature reaches the maximum temperature, the
zone heating is disabled.
Comfort this function serves to maintain comfort oor temperature. The controller monitors the oor temperature and
disables the zone heating when zone temperature reaches the maximum temperature in order to prevent
overheating. When the oor temperature drops below the pre-set minimum temperature, the zone heating will be
enabled.
4.4 MAXIMUM TEMPERATURE/MINIMUM TEMPERATURE
Minimum temperature can only be set if the operation mode is set to “Comfort”.
Max. and min. temperatures must be set when using the oor sensor. In mode “Floor protection” (setting range 20 - 35°C) and in mode “Comfort”
(setting range 5 - 27°C).
If mode set to “Floor heating protection” you must set the “Max. temperature” for the oor sensor.
Choose “Max. temperature” using ▼ – pres MENU. Set temperature with ▼ or ▲ – press MENU. Press MENU to “CONFIRM” or choose “CANCEL”
with ▲ – press MENU.
If mode set to “Comfort” you must set both the “Min. temperature” and the “Max. temperature” for the oor sensor.
Choose “Min. temperature” using ▼ – pres MENU. Set temperature with ▼ or ▲ – press MENU. Press MENU to “CONFIRM” or choose “CANCEL”
with ▲ – press MENU.
Then choose “Max. temperature” using ▼ – pres MENU. Set temperature with ▼ or ▲ – press MENU. Press MENU to “CONFIRM” or choose “CAN-
CEL” with ▲ – press MENU.
4.5 HYSTERESIS
Floor temperature hysteresis denes the tolerance of the oor tempearture in order to prevent undesired oscillation in case of small temperature
uctuations (within the range 0,1 to minus 5°C).
Example:
Maximum oor temperature: 45°C Hysteresis: 2°C
The controller will disconnect to the oor sensor when the temprature exceeds 45°C. When the temperature starts falling, the connection will be
enabled again when the temperature is dropped to 43°C (unless the room temeperature has been reached).
4.6 CALIBRATION
Floor sensor can be calibrated if the measured oor temperature displayed diers from the actual measured temperature (best to use an infrared
thermometer). Calibration setting range is from -10°C to +10°C with the accuracy of 0,1°C.
Choose “Calibration” using ▼ – pres MENU. Set “Degrees” with ▼ or ▲ – press MENU. Press MENU to “CONFIRM” or choose “CANCEL”
with ▲ – press MENU.