EasyManua.ls Logo

Samson 3374-11 - Page 46

Samson 3374-11
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46 EB 8331-4 EN
Operating level
PID controller application
The set point adjustable at the actuator is used to position the valve using a PID algorithm.
The input signal is used as the process variable. The PID controller is adjusted using the pa-
rameters: Proportional-action coefcient Kp, Reset time Tn, Derivative-action time Tv and Op-
erating point Y
0
:
The proportional-action coefcient Kp acts as gain.
The reset time Tn is the time it takes for the integral component during a step response in a PI
controller to produce a change in the manipulated variable identical to the change produced
by the P component. Increasing the reset time Tn reduces the rate of change in the output
when the set point deviation is constant.
The derivative-action time Tv is the time it takes the rise response of a PD controller to reach a
certain manipulated variable value earlier than it would take the response with the P compo-
nent only. Increasing the derivative-action time Tv causes an increase in the manipulated
variable amplitude when the rate of change is constant. After ramped changes of the set
point deviation, a longer derivative-action time Tv causes the D component to have a longer
effect.
The operating point Y
0
determines the positioning value, which is fed to the controlled system
when the process variable is the same as the set point. The operating point is normally only
important for P and PD controllers, but it can also be set for control strategies PI, PID and I
due to the possible limitation of the integral-action component. For control strategies with in-
tegral-action component, the operating point can also be used as the initial value for a re-
start.
Î Set Code 6 to PID.
Î Use terminal assignment according to Fig.17.
Two-step mode application
The binary input IN2 is used for this function. When the binary input is in the active switch-
ing state, the actuator stem retracts to 100% of the adjusted travel range. When the binary
input is in the inactive switching state, the actuator stem moves to the closed position (0%).
Î Set Code 6 to 2STP.
Î Use terminal assignment according to Fig.18.
Three-step mode application
The binary input IN2 is used for this function to retract the actuator stem and binary input
IN3 to extend the actuator stem.
Î Set Code 6 to 3STP.
Î Use terminal assignment according to Fig.19.

Table of Contents

Related product manuals