54 EB 8331-4 EN
Congurationlevel
9.4.2 Operatingdirectionincreasing/decreasing
− Endpositionguiding(stemretracts)(c35): The actuator stem moves the valve to the low-
er end position if the input signal reaches the value entered in this code. Setting c35 =
100.0% causes this function with a retracting actuator stem to be deactivated.
− Endpositionguiding(stemextends)(c36): The actuator stem moves the valve to the top
end position if the input signal reaches the value entered in this code. Setting c36 =
0.0% causes this function with an extending actuator stem to be deactivated.
Code Description WE Adjustment range
c35 End position guiding
(stem retracts)
97.0 % 50.0 to 100.0%
c36 End position guiding (stem extends) 1.0 % 0.0 to 49.9%
9.5 Position feedback signal
The position feedback indicates the actuator stem position, which is issued as an analog sig-
nal at the terminals U OUT or I OUT. The span of the position feedback signal is adjusted
over the lower and upper range value parameters.
− At least 2.5V or 5mA (depending on the input signal used) must separate the upper and
lower range values.
− When c37 = YES, the position feedback signal is 12V or 24mA in the event of a fault.
− During initialization, transit time measurement or zero calibration, the position feedback
signal = 0V or 0mA.
Code Description WE Adjustment range
c05 Unit mA mA (current signal)
V (voltage signal)
c06 Lower range value 4.0mA 0.0 to 7.5V or 0.0 to 15.0mA
c07 Upper range value 20.0mA 2.5 to 10.0V or 5.0 to 20.0mA
c37 Superimposing an error message NO YES (error reading active)
NO (error reading inactive)
Note