50 EB 8331-4 EN
Congurationlevel
9 Congurationlevel
The actuator is adapted to its control task in the conguration level. The codes in this level
have a 'c' prex to identify them.
All the parameters of the conguration level are listed in section17.2.2 on page83.
9.1 Activating and setting parameters
Changingsettingsinthecongurationlevel
Activatethecongurationlevel
1. Turn (when the start screen appears) to select Code 10.
2. Press to activate the conguration level.
Change parameter setting (example shown: source Code c01)
1. Press
. The reading blinks on the display.
2. Turn until the required setting is reached.
3. Press
to conrm the setting.
Exitcongurationlevel
1. Turn
to select the code c00.
2. Press to conrm the setting.