EasyManua.ls Logo

Samson 3374-11 - 9.3 Operating direction

Samson 3374-11
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52 EB 8331-4 EN
Congurationlevel
Internalpositioningvalue(c32=INT): The actuator stem moves to the position specied
in Code c33 upon failure of the input signal.
Lastposition(c32=LAST): The actuator stem remains in the last position that the valve
moved to before failure of the input signal.
The error message is reset and the actuator returns to closed-loop operation if the input sig-
nal moves within 0.2V or 0.4mA of the lower range value.
Code Description WE Adjustment range
c31 Detect input signal failure NO NO (function inactive)
YES (function active)
c32 Positioning value upon input signal fail-
ure
INT INT (internal positioning value)
LAST (last position)
c33 Internal positioning value 0.0 % 0.0 to 100.0%
9.3 Operating direction
Î See Fig.21 on page53.
Increasing/increasing(c42=>>):
The actuator stem retracts as the input signal increases.
Increasing/decreasing(c42=<>):
The actuator stem extends as the input signal increases.
Actuator stem extended
With globe valves: Valve closed
With three-way mixing valves: Port A à AB open, B à AB closed
With three-way diverting valves: Port AB à A closed, AB à B open
Actuator stem retracted
With globe valves: Valve open
With three-way mixing valves: Port A à AB closed, B à AB open
With three-way diverting valves: Port AB à A open, AB à B closed

Table of Contents