84 EB 8331-4 EN
Decommissioning and disassembly
Code
Parameters Setting range (select ESC to cancel) WE Section Customer
data
c12 Logic NINV (not inverted)
INV (inverted)
NINV 9.6
Binary output
c15 Function NONE (inactive)
FAIL (indicate error during operation)
LIM (electronic limit contact)
PRIO (priority position reached)
BIN (adopt binary input)
MAN (indicate manual mode)
NONE 9.7
c16 Logic NINV (not inverted)
INV (inverted)
NINV 9.7
Electronic limit contact (binary output)
c21 Message in case of event NONE (inactive)
HIGH (value above limit)
LOW (value below limit)
NONE 9.7
c22 Switching point 0.0 to 100.0% 10.0 % 9.7
c23 Hysteresis 0.0 to 10.0% 1.0 % 9.7
Electronic limit contact 1
c24 Message in case of event NONE (inactive)
HIGH (value above limit)
LOW (value below limit)
NONE 9.8
c25 Switching point 0.0 to 100.0% 10.0 % 9.8
c26 Hysteresis 0.0 to 10.0% 1.0 % 9.8
Electronic limit contact 2
c27 Message NONE (inactive)
HIGH (value above limit)
LOW (value below limit)
NONE 9.8
c28 Switching point 0.0 to 100.0% 90.0 % 9.8
c29 Hysteresis 0.0 to 10.0% 1.0 % 9.8
Input signal
c31 Detect input signal failure NO
YES
NO 9.2
c32 Positioning value upon in-
put signal failure
INT (internal positioning value)
LAST (last position)
INT 9.2
c33 Internal positioning value 0.0 to 100.0% 0.0 % 9.2
c34 Travel for priority position 0.0 to 100.0% 0.0 % 9.6

Table of Contents