86 EB 8331-4 EN
Decommissioning and disassembly
Code
Parameters Setting range (select ESC to cancel) WE Section Customer
data
Characteristic
c71 Characteristic type LIN (linear)
EQUA (equal percentage)
INV (reverse equal percentage)
USER (user-dened)
LIN 9.12
c72 User-dened characteristic User-dened 9.12
PID controller
c80 Operating point Y
0
0 to 100% 0% 8.4
c81 Set point 0.0 to 100.0% 50.0 % 8.4
c82 Proportional-action coef-
cient KP
0.1 to 50.0 1.0 8.4
c83 Reset time Tn 0 to 999 s 20s 8.4
c84 Derivative-action time Tv 0 to 999 s 0s 8.4
Scaling of the set point for PID controller
c85 Unit NONE (none)
PER (%)
CEL (°C)
BAR (bar)
PER
c86 Lower range value –999 to 999 0
c87 Upper range value –999 to 999 100
Process variable adjustment
c88 Lower limit of range Depending on c85 (see above) 0
c89 Upper limit of range Depending on c85 (see above) 100
Set point deviation
c90 Function 0: Not inverted; 1: Inverted 0
Actuator
c91 Customized key number
active
NO
YES
NO 7.4.1
c92 Customized key number 0000 to 1999 0000 7.4.1
c93 Backlight always on NO
YES
NO 8.2.2
c94 Key number is active NO
YES
NO 7.4