96 EB 8331-4 EN
Decommissioning and disassembly
Class Designation COILS (1-bit) Access Status 0 Status 1
Limit contact
10 Torque switch: Actuator stem retracted R Off On
11 Torque switch: Actuator stem extended R Off On
Binary output
12 Logical state of binary output R Off On
13 Binary output (switching contact) R Off On
14 Enable manual level of control station (binary output) R/W No Yes
15 Logical state of binary output (manual level of control station) R/W Off On
Fatal error
16 Final test failed R No Yes
17 Plausibility error R No Yes
18 Motor or potentiometer not turning R No Yes
19 Both limit contacts are active R No Yes
20 Retracting of actuator stem canceled R No Yes
21 Extending of actuator stem canceled R No Yes
22 Blockage R No Yes
23 Input signal failure R No Yes
24 Sensor failure R No Yes
EEPROM error
25 Basic setting: state R No Yes
26 Basic setting: cause R Read error Write error
27 Settings: state R No Yes
28 Settings: cause R Read error Write error
29 Calibration: state R No Yes
30 Calibration: cause R Read error Write error
31 Potentiometer calibration: state R No Yes
32 Potentiometer calibration: cause R Read error Write error
33 Serial number: state R No Yes
34 Serial number: cause R Read error Write error
35 Manufacturing parameter: state R No Yes
36 Manufacturing parameter: cause R Read error Write error
37 Transit time: state R No Yes
38 Transit time: cause R Read error Write error
39 Status messages: state R No Yes
40 Status messages: cause R Read error Write error
41 Statistics: state R No Yes
42 Statistics: cause R Read error Write error