EasyManua.ls Logo

Samson 3730 Series - Page 84

Samson 3730 Series
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
84 EB 8389-1S EN
Full stroke test (FST)
The 'Tolerance limit' parameter denes the
permitted valve positions for the start value
and the end value for the step.
The 'Sampling time' denes the time interval
between which the measured values are re-
corded during the test.
Test cancelation conditions
Various cancelation conditions provide addi-
tional protection against the valve slamming
shut or moving past the end position. The
positioner cancels the full stroke test when
one of the following cancelation conditions is
fullled:
'Max. test duration': The test is canceled
when the maximum permissible test du-
ration is reached.
'Max. breakaway time': The test is can-
celed when the time entered in 'Settling
time before starting test' has elapsed and
the valve has still not changed its posi-
tion. This cancelation condition only be-
comes effective after it has been activat-
ed ("Activate 'Max. breakaway time" =
[Yes]).
Operating point +
Tolerance limit
Operating point –
Tolerance limit
Operating point
Settling time before
starting test
Waiting time after
step change
t
decreasing
t
increasing
Waiting time after
step change
Settling time before
starting test
Waiting time after
step change
Waiting time after
step change
100
t [s]
x [%]
t
decreasing
‘Lower range value’ – ‘Stop’
x ‘Ramp time (decreasing)’
100
t
increasing
‘Step start’ – ‘Step end’
x ‘Ramp time (increasing)’
100
Fig. 20: Course of the full stroke test with step response (left) and ramp function (right), fail-close

Table of Contents

Other manuals for Samson 3730 Series

Related product manuals