16-2 EB 8384-3 EN
Code
no.
Parameter–Readings/
values [default setting]
Description
5* Nominal range
mmorangle°,ESC
Nominal valve travel or opening angle must be entered for nominal
(NOM) or substitute (SUb) initialization.
The possible adjustment range depends on the pin position from the
tableforCode4.
Indicatesmaximumtravel/anglereachedduringinitializationafter
initialization has been successfully completed.
6* Init mode
[MAX] Maximum range
NOM Nominal range
MAN Manual setting
SUb Emergency mode
ZP Zero calibration
ESC Cancel
Select the initialization mode
MAX: Travel/angleoftheclosurememberfromtheCLOSED
position to the opposite stop in the actuator.
NOM: Travel/angleoftheclosuremembermeasuredfromthe
CLOSED position to the indicated OPEN position.
MAN: Manually selected range
SUb: Substitute calibration (without initialization)
7* w/x
[ää] Increasing/
increasing
äæ
Increasing/
decreasing
ESC
Directionofactionofthesetpointwinrelationtothetravel/anglex
Automatic adaptation:
AIR TO
OPEN:
On completing initialization, the direction of action re-
mainsincreasing/increasing(ää). A globe valve opens
as the set point increases.
AIR TO
CLOSE:
On completing initialization, the direction of action chang-
estoincreasing/decreasing(äæ). A globe valve closes as
the set point increases.
8*
Travel/angle range start
(lower x-range value)
[0.0]to80.0%ofthe
nominal range, ESC
Specied in mm or angle °
provided Code4 is acti-
vated.
Lowerrangevaluefortravel/angleinnominaloroperatingrange
The operating rangeistheactualtravel/angleofthevalveandis
limitedbythelowertravel/anglerangevalue(Code8)andtheup-
pertravel/anglerangevalue(Code9).
Usually, the operating range and the nominal range are identical.
The nominal range can be limited to the operating range by the low-
er and upper x-range values.
The value is displayed or must be entered.
Thecharacteristicisadapted.SeealsotheexampleinCode9.