1-3. Real function data
(1) Select the exact capacity according to outdoor unit model and combination
rate using outdoor unit capacity table. According to given indoor and
outdoor temperature, find outdoor unit capacity and power input using
the table. Each indoor unit capacity (power input) is calculated as follow.
IUC=OUC x INX/TNX IUC: Each indoor unit capacity (power input)
OUC: Outdoor unit capacity (power input) INX: Each indoor unit capacity index
TNX: Total capacity index
(2) If the capacity is smaller than the load, change unit to a larger capacity
indoor unit and repeat the selection process.