USER MANUAL
28/97
2.3.9.1. 2T VOLTAGE CLASS
Cable Cross-
section Fitting
the Terminal
Cable Cross-
section to Mains
and Motor Side
Fast Fuses
(700V) +
Disc. Switch
12.5
0.5÷10
(20÷6AWG)
10 1.2-1.5
2.5 (12AWG)
16 16 25
17 10 1.2-1.5
4 (10AWG)
20 25 25
27 10 1.2-1.5
8 (8AWG)
32 32 45
38
0.5÷25
(20÷4AWG)
18 2.5 10 (6AWG) 63 63 60
51 18 2.5 16 (5AWG) 80 80 80
65 18 2.5
25 (4AWG)
80 80 80
88
25÷50
(3÷1/0AWG)
24 6-8 35 (2AWG) 125 125 125
103 24 6-8
50 (1/0AWG)
125 125 125
180
35÷185
(2AWG÷
350kcmils)
30 10 95 (4/0AWG) 250 200 250
300 Bus bar - 30 185 (400kcmils) 350 400 400
345 Bus bar - 30 240 (500kcmils) 500 400 450
Always use the correct cable cross-
sections and activate the protective devices provided
for the inverter. Failure to do so will cause the non-
compliance to standard regulations of
the system where the inverter is installed.