BASIC
USER MANUAL
SINUS PENTA
47/97
5.4. Warnings
Warning messages are displayed on the display/keypad. They are flashing messages that usually appear in line 1 or 2 on
the display.
NOTE
Warnings are neither protections nor alarms, and are not stored to the Fault list.
Warning
Message
Description
W03
SEARCHING… The user interface is searching the data of the next page to display.
W04
DATA READ KO Software warnings concerning data
reading
.
W06
HOME SAVED The page displayed has been saved as the home page displayed at power on.
W07
DOWNLOADING
The keypad is writing to the drive the WORK zone parameters saved to its own flash
memory.
W08
UPLOADING
The keypad is reading from the drive the WORK zone parameters that will be saved
to its own flash memory.
W09
DOWNLOAD OK Parameters were successfully downloaded (
written
) from the keypad to the drive.
W11
UPLOAD OK Parameters were successfully uploaded (
read
) from the drive to the keypad.
W12
UPLOAD KO
The keypad interrupted parameter upload to the drive.
Parameter reading has failed.
W13
NO DOWNLOAD
A Download procedure was queried, but no parameter is saved to the flash
memory.
W16
PLEASE WAIT… Wait until the system completes the operation required.
W17
SAVE IMPOSSIBLE Parameter save is not allowed.
W18
PARAMETERS LOST
The keypad interrupted parameter download to the drive. Parameter writing has
failed. As a result, not all parameters have been updated (parameter inconsistency).
W19
NO PARAMETERS LOAD UPLOAD impossible.
W20
NOT NOW The required function is not available at the moment.
W21
CONTROL ON The required function is inhibited because the drive is running.
W23
DOWNLOAD VER. KO
Download failed because parameters saved to keypad memory relate to a SW
version or product ID incompatible with the drive SW version or product ID.
W24
VERIFY DATA
Download preliminary operation underway, the system is checking the integrity and
compatibility of the parameters saved in the keypad memory.
W28
OPEN START Open and close the
START
(MDI1) signal
to start the drive.
W31
ENCODER OK Encoder tuning procedure finished: the encoder is correctly connected.
W32
OPEN ENABLE Open and close the
ENABLE
(MDI2) signal to enable the drive.
W33
WRITE IMPOSSIBLE Writing procedure impossible.
W34
ILLEGAL DATA Illegal value entered, operation failed.
W35
NO WRITE CONTROL Writing procedure impossible because Control is active and the drive is running.
W36
ILLEGAL ADDRESS Illegal address entered, operation failed.
W37
ENABLE LOCKED
The drive is disabled and does not acknowledge the ENABLE command because it
is writing a “C” parameter.
CAUTION
The drive will start up as soon as writing is over!!!
W38
LOCKED
Editing mode cannot be accessed because parameter modification is disabled:
P000 is different from P002.

Table of Contents