2.3.3. POWER TERMINALS / BARS
Inputs for three-phase supply (the phase sequence is not important)
Three-phase motor outputs
Link to the DC voltage positive pole. It can be used for
-DC voltage supply;
- DC reactor;
-
the external braking resistor and the external braking unit (for the drive models which are NOT
dedicated to the external braking resistor)
- the external braking unit.
When fitted, link to the positive pole of the continuous AC rectified voltage. It can be used for the
DC reactor—if no DC reactor is used, terminal 47/D must be short-circuited to terminal
using a cable/bar having the same cross-section as the cables used for pow
er supply; factory
setting).
When available, it can be used to connect the IGBT brake for braking resistors.
Link to the negative pole of the DC voltage. It can be used for DC power supply and the external
braking unit (for the drive models which are NOT provided with terminal
52/- dedicated to the
external braking unit).
When available, it can be used to connect the positive pole of the DC voltage to be used for the
external braking resistor only.
S05 (4T)-S15-S20 Terminal board:
S05 (2T) Terminal board:
are short-circuited as a factory setting. The DC choke,
if any, shall be linked between bars
after removing the short-circuit.
If DC supply is required and if an external
braking resistor is to be installed, remove
the short-circuit between
if an external braking resistor is to be installed.