SINUS PENTA
BASIC
USER MANUAL
30/97
(continued)
Size
SINUS
PENTA
Model
Inverter
Rated
Current
Cable Cross-
section Fitting
the Terminal
Cable
Stripping
Tightening
Torque
Cable Cross-
section to Mains
and Motor Side
Fast Fuses
(700V) +
Disc. Switch
Magnetic
Circuit
Breaker
AC1
Contactor
A
mm
2
(AWG/kcmils)
mm
Nm
mm
2
(AWG/kcmils)
A
A
A
S41
0180
300 Bus bar - 30 185 (400kcmils) 350 400 400
0202
345 Bus bar - 30 240 (500kcmils) 500 400 450
0217
375 Bus bar - 30
2x120
(2x4/0AWG)
550 630 450
0260
425 Bus bar - 30
2x120
(2x250kcmils)
630 630 500
S51
0313
480 Bus bar - 50
2x150
(2x300kcmils)
700 630 550
0367
550 Bus bar - 50
2x185
(2x350kcmils)
800 800 600
0402
680 Bus bar - 50
2x240
(2x500kcmils
1000 800 700
S60
0457
720 Bus bar - 50
3x150
(3x300kcmils)
1000 800 800
0524
800 Bus bar - 50
3x185
(3x350kcmils)
1000 1000 1000
S65
0598
900 Bus bar -
M10: 50
M12: 110
3x240
(3x500kcmils)
1250 1250 1000
0748
1000 Bus bar -
M10: 50
M12: 110
3x240
(3x500kcmils)
1250 1250 1200
0831
1200 Bus bar -
M10: 50
M12: 110
4x240
(4x500kcmils)
1600 1600 1600
S75
0964
1480 Bus bar -
M10: 50
M12: 110
6x150
(6x300kcmils)
2x1000 2000 2x1000
1130
1700 Bus bar -
M10: 50
M12: 110
6x185
(6x350kcmils)
2x1250 2000 2x1200
1296
2100 Bus bar -
M10: 50
M12: 110
6x240
(6x500kcmils)
2x1250 2500 2x1200
S90
1800
2600 Bus bar -
M10: 50
M12: 110
9x240
(3x500kcmils)
3x1250 4000 3x1000
2076
3000 Bus bar -
M10: 50
M12: 110
9x240
(3x500kcmils)
3x1250 4000 3x1200
CAUTION
Always use the correct cable cross-
sections and activate the protective devices provided
for the inverter. Failure to do so will cause the non-
compliance to standard regulations of
the system where the inverter is installed.