EasyManua.ls Logo

Schiedel CM03 - Commissioning; General; Manual operation; Mechanical default settings, preparation

Default Icon
99 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Commisioning
Operating Manual 90° ACTUSAFE CMF(S)QT
OM-ENGLISH-Failsafe-QT-16xx-V2.00-2022.03.01
Figure 24: Terminal box: 1. . . Metric screw M40x1,5, 2. . . 2 pcs. M20x1,5, 3. . . Terminals for the control signals,
4. . . Terminals for the power supply, 5. . . Terminal for ground connection, 6. . . Outside ground connection
CAUTION: If, during outdoor installation, commissioning is not carried out immediately after electrical connec-
tion, the power supply must be connected at a minimum to achieve a heating effect. In this case, the silica gel
may remain in the connection compartment until commissioning. See section 3.3, page 26.
5 Commisioning
Before commissioning, ensure that the actuator is correctly assembled and electrically connected (see section 4, page 27).
NOTE: Remove silica gel from the connection compartment.
5.1 General
CAUTION: During commissioning and after every disassembly of the actuator, the electric end positions (see
section 5.5, page 31) must be reset.
5.2 Manual operation
The use of a differential gearbox in the handwheel assembly makes mechanical switching unnecessary during manual
operation.
CAUTION: Manual operation with mechanical or electromechanical equipment (such as: lever, drilling machine,
etc.) is NOT ALLOWED, as this may damage the product.
5.3 Mechanical default settings, preparation
The use of multi-turn sensors makes mechanical settings unnecessary.
CAUTION: Before the motorised operation of the valve, it is essential to check and eventually adjust torque
settings.
32

Table of Contents