5.16
SEL-700G Relay Instruction Manual Date Code 20170814
Metering and Monitoring
Breaker Monitor
These three points are entered with the settings in Table 5.11.
Table 5.11 Breaker Monitor Settings
a
a
n=X or Y.
Setting Prompt Setting Range
Setting Name :=
Breakern Monitor (Y, N) EBMONn := Y
nCL/OPN OPS SETPT 1 (0–65000) COSP1n := 10000
b
b
COSP1n must be set greater than COSP2n.
nCL/OPN OPS SETPT 2 (0–65000) COSP2n := 150
cd
c
COSP2n must be set greater than or equal to COSP3n.
d
If COSP2n is set the same as COSP3n, then KASP2 must be set the same as KASP3n.
nCL/OPN OPS SETPT 3 (0–65000) COSP2n := 12
nkA PRI INTERRPTD 1 (0.10–999.00 kA) KASP1n := 1.20
e
e
KASP1n must be set less than KASP2n.
nkA PRI INTERRPTD 2 (0.10–999.00 kA) KASP2n := 8.00
nkA PRI INTERRPTD 3 (0.10–999.00 kA) KASP3n := 20.00
f
f
KASP3n must be set at least five times (but no more than 100 times) the KASP1n setting
value.
BRKRn MON CONTROL SELOGIC BKMONn := TRIP