EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-700G1 - AC;DC Control Connection Diagrams; Figure 2.13 Analog Output Wiring Example; Figure 2.14 Output OUT103 Relay Output Contact Configuration

Schweitzer Engineering Laboratories SEL-700G1
824 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.23
Date Code 20170814 Instruction Manual SEL-700G Relay
Installation
AC/DC Control Connection Diagrams
Figure 2.13 Analog Output Wiring Example
AC/DC Control Connection Diagrams
This section describes fail-safe versus nonfail-safe tripping, describes voltage
connections, and provides the ac and dc wiring diagrams.
Fail-Safe/Nonfail-Safe
Tripping
Figure 2.14 shows the output OUT103 relay coil and Form C contact. When the
relay coil is de-energized, the contact between A07 and A08 is open while the
contact between A07 and A09 is closed.
Figure 2.14 Output OUT103 Relay Output Contact Configuration
The SEL-700G provides fail-safe and nonfail-safe trip modes (setting
selectable) for all output contacts. The following occurs in fail-safe mode:
➤ The relay coil is energized continuously if the SEL-700G is
powered and operational.
➤ When the SEL-700G generates a trip signal, the relay coil is de-
energized.
➤ The relay coil is also de-energized if the SEL-700G power
supply voltage is removed or if the SEL-700G fails (self-test
status is FAIL).
Figure 2.15 shows fail-safe and nonfail-safe wiring methods to control
breakers.
Analog Output
Relay Chassis Ground
Meter
or
PLC
AO_0 1
02
01
NOTE: When using fast hybrid
output contacts, do not use the
FAILSAFE mode.
NOTE: Fast hybrid contacts are
designed for fast closing (50 s) only.
Fail-safe mode operating time (time
to open the contacts) for fast hybrid
contacts is <8 ms (the same time as
for a normal output contact).
Contacts shown with
OUT103 relay coil de-energized
A07
A08 A09
OUT103
Relay Coil

Table of Contents