7.42
SEL-700G Relay Instruction Manual Date Code 20170814
Communications
SEL ASCII Protocol and Commands
Table 7.49 SHOW Command Format
Parameter Description
s Appends, s, the name of the specific setting you want to view, and jumps to
this setting. If s is not entered, the relay starts at the first setting.
=>>SHO <Enter>
Group 1
Relay Settings
ID Settings
RID := SEL-700GT
TID := INTERTIE RELAY
Config Settings
PHROT := ABC CTRX := 500 INOM := 5.0
DELTAY_X := WYE PTRX := 100.00 VNOM_X := 13.80
CTRY := 500 DELTAY_Y := WYE PTRY := 100.00
VNOM_Y := 13.80 PTRS := 100.00 CTRN := 100
Gnd Differential
E87N := N
Res Earth Fault
EREF := N
Rotor Ground
E64F := N
System Backup
EBUP := V
Volt-Restr TOC
51VP := 8.00 51VCA := 0 51VC := U2
51VTD := 3.00 51VRS := Y
51VTC := NOT LOPX
Loss of Field
E40 := Y 40Z1P := 13.4 40XD1 := -2.5
40Z1D := 0.00 40Z2P := 13.4 40XD2 := -2.5
40Z2D := 0.50
40ZTC := NOT LOPX
Curr Unbalance
E46 := Y 46Q1P := 8.0 46Q1D := 30.00
46Q2P := 8.0 46Q2K := 10
46QTC := 1
4
Thermal Overload
E49T := N
Volts per Hertz
E24 := Y 24D1P := 105 24D1D := 1.00
24CCS := ID 24IP := 105 24IC := 2
24ITD := 0.1 24D2P2 := 176 24D2D2 := 3.00
24CR := 240.00
24TC := 1
Inadv Enrgzation
EINAD := N
X Side Phase IOC
50PX1P := OFF 50PX2P := OFF 50PX3P := OFF
X Side Res IOC
50GX1P := OFF 50GX2P := OFF
XSide NegSeq IOC
50QX1P := OFF 50QX2P := OFF
X Side Res TOC
51GXP := OFF
Y Side Phase IOC
50PY1P := OFF 50PY2P := OFF 50PY3P := OFF
Y Side Res IOC
50GY1P := OFF 50GY2P := OFF
YSide NegSeq IOC
50QY1P := OFF 50QY2P := OFF
Figure 7.26 SHOW Command Example