F.34
SEL-700G Relay Instruction Manual Date Code 20170814
IEC 61850 Communications
Logical Nodes
Table F.18 shows the LN associated with control elements defined as Logical
Device CON.
Table F.19 shows the LN associated with annunciation elements defined as
Logical Device ANN.
THERMMTHR1 MaxOthTmp.instMag.f RTDOTHMX
c
Other maximum RTD temperature
THERMMTHR1 Tmp01.instMag.f–
Tmp12.instMag.f
RTD1–RTD12
c
RTD1–RTD12 temperature
Functional Constraint = ST
THERMMTHR1 EEHealth.stVal RTDFLT?1:3
c
RTD input or communication status
a
MX values contain instantaneous attributes (instMag) and instCVal), which are updated whenever the source updates and other attributes
which are only updated when the source foes outside the data source’s deadband (mag and cVal). Only the instantaneous values are shown
in the table.
b
Data validity depends on the relay model and installed card options. Refer to Section 1: Introduction and Specifications for different relay
models of available card options. Refer to Section 5: Metering and Monitoring for the model dependent metering quantities.
c
Valid data depends on E49RTD and RTD1LOC–RTD12LOC.
Table F.17 Logical Device: MET (Metering) (Sheet 7 of 7)
Logical Node Attribute Data Source Comment
Table F.18 Logical Device: CON (Remote Control)
Logical Node Status Control Relay Word Bit Comment
RBGGIO1 SPCSO01.stVal–
SPCSO08.stVal
SPCSO01.Oper.ctlVal–
SPCSO08.Oper.ctlVal
RB01–RB08 Remote Bits RB01–RB08
RBGGIO2 SPCSO09.stVal–
SPCSO16.stVal
SPCSO09.Oper.ctlVal–
SPCSO16.Oper.ctlVal
RB09–RB16 Remote Bits RB09–RB16
RBGGIO3 SPCSO17.stVal–
SPCSO24.stVal
SPCSO17.Oper.ctlVal–
SPCSO24.Oper.ctlVal
RB17–RB24 Remote Bits RB17–RB24
RBGGIO4 SPCSO25.stVal–
SPCSO32.stVal
SPCSO25.Oper.ctlVal–
SPCSO32.Oper.ctlVal
RB25–RB32 Remote Bits RB25–RB32
Table F.19 Logical Device: ANN (Annunciation) (Sheet 1 of 5)
Logical Node Attribute Data Source Comment
Functional Constraint = DC
DevIDLPHD1 PhyNam.model PARTNO Part number
Functional Constraint = MX
a
AINCGGIO21 AnIn01.instMag.f–
AnIn04.instMag.f
AI301–AI304
b
Analog Inputs (AI301 to AI304)—Slot C
AINDGGIO22 AnIn01.instMag.f–
AnIn04.instMag.f
AI401–AI404
b
Analog Inputs (AI401 to AI404)—Slot D
AINEGGIO23 AnIn01.instMag.f–
AnIn04.instMag.f
AI501–AI504
b
Analog Inputs (AI501 to AI504)—Slot E
BWXASCBR1 AbrPrt.instMag.f WEARAX X Breaker–Contact A wear
BWXBSCBR2 AbrPrt.instMag.f WEARBX X Breaker–Contact B wear
BWXCSCBR3 AbrPrt.instMag.f WEARCX X Breaker–Contact C wear
BWYASCBR4 AbrPrt.instMag.f WEARAY Y Breaker–Contact A wear
BWYBSCBR5 AbrPrt.instMag.f WEARBY Y Breaker–Contact B wear
BWYCSCBR6 AbrPrt.instMag.f WEARCY Y Breaker–Contact C wear