2.38
SEL-700G Relay Instruction Manual Date Code 20170814
Installation
Field Serviceability
Real-Time Clock
Battery Replacement
To replace the real-time clock battery, perform the following steps:
Step 1. De-energize the relay.
Step 2. Remove the four rear-panel screws and the relay rear panel.
Step 3. Remove the Slot B printed circuit board.
Step 4. Locate the battery clip (holder) on the board.
Step 5. Carefully remove the battery from beneath the clip.
Properly dispose of the old battery.
Step 6. Install the new battery with the positive (+) side facing up.
Step 7. Insert the printed circuit board into Slot B.
Step 8. Replace the relay rear panel and energize the relay.
Step 9. Set the relay date and time.
CAUTION
There is danger of explosion if the
battery is incorrectly replaced.
Replace only with Ray-O-Vac no.
BR2335 or equivalent recommended
by manufacturer. See Owner's Manual
for safety instructions. The battery
used in this device may present a fire
or chemical burn hazard if
mistreated. Do not recharge,
disassemble, heat above 100°C or
incinerate. Dispose of used batteries
according to the manufacturer’s
instructions. Keep battery out of
reach of children.