Screen
no.
Screen Data displayed
G 7
AIR PREHEATING
10 seconds
24/08/2005 13:12
Operating phase - air preheating prior to starting
generating set
Countdown for air preheating delay
Date and time (depending on settings)
Generating set started
Screen
no.
Screen Data displayed
G 8
Default
screen
AVAILABLE POWER
75%
24/08/2005 13:12
Operating phase – generating set in operation –
stable voltage and frequency
Available power
Date and time (depending on settings)
G 9
AUTOMATIC STOP
IN PROGRESS
LOAD SUPPRESSION
1 min 30 sec
24/08/2005 13:12
Operating mode - operation in Auto Mode
Opening of power supply device (motorised circuit
breaker or source changeover switch controlled by
TELYS)
Countdown for the mains return delay OR the load
test delay
Date and time (depending on settings)
G 10
AUTOMATIC STOP
IN PROGRESS
COOLING DOWN
1 min 30 sec
24/08/2005 13:14
Operating mode - operation in Auto Mode
Generation set cooling in progress
Countdown for Engine Stop delay (cooling) OR
Gradual Stop delay (Coolant temperature) OR
Overload Gradual Stop delay OR OFF load test
delay
Date and time (depending on settings)