English 23
General settings:
Para-
meter
Parameter name Parameter description Setup range Default value
P1.1 AUTOMATIC SWITCHO-
VER SUMMER/WINTER
Automatic switch-on or switch-off of heating
depending on the average one-day outdoor tem-
perature can be enabled with the setup.
0–NO
1–YES 1
P1.2 AVERAGE OUTDOOR
TEMPERATURE FOR
SUMMER/WINTER
SWITCHOVER
Set up the average one-day outdoor temperature
by which the heating automatically switches off or
on.
10 ÷ 30°C
18
P1.3 OUTDOOR TEMPERA-
TURE BY WHICH
FROST PROTECTION
WILL ACTIVATE
Set up the value of the outdoor temperature by
which the frost protection will activate. The boiler
operates with at least minimum temperature.
-30 ÷ 10°C
2
P1.4 REQUESTED ROOM
TEMPERATURE BY
FROST PROTECTION
Set up the requested room temperature if the
heating is switched off.
2 ÷ 12°C
6
P1.5 TEMPERATURE ROUND
UP
Set up to which value the measured temperatures
should be rounded up.
0–0.1°C
1–0.2°C
2–0.5°C
3–1°C
2
P1.6 AUTOMATIC SHIFT OF
CLOCK TO SUMMER/
WINTER TIME
Based on the calendar, the controller automatically
shifts the clock to summer or winter time.
0–NO
1–YES 1
P1.7 PERIOD OF TEM-
PERATURE LOGGING
(MINUTES)
With the setup, a time interval for saving the mea-
sured temperature values can be selected.
1 ÷ 30MIN
5
P1.8 TONES Set up the tones of the controller. 0–OFF
1–ON
1
P1.9 ADVANCED TEMPERA-
TURE SCREEN
The advanced temperature screen means that the
measured and requested or calculated temperature
value is displayed in the temperature review.
0–NO
1–YES
1
P1.10 LEVEL OF PROTEC-
TION AGAINST FROST
The setup is to determine the level of frost
protection that depends on the assessment of the
possibility of freezing.
Select level 0, if there is no possibility of freezing of
the building.
Select level 1, if there is a possibility of freezing of
the building and no room sensor is connected.
Select level 2, if there is a possibility of freezing of
the building and a room sensor is connected.
Select level 3, if the possibility of freezing of the
building is major due to individual parts of the heat-
ing system being particularly exposed to freezing.
0–NO PRO-
TECTION
1–LEVEL 1
2–LEVEL 2
3–LEVEL 3
(GREATEST
PROTECTION)
1
P1.11 COMPENSATION OF
THE EFFECT OF BUILD-
ING ON OUTDOOR TEM-
PERATURE SENSOR
With the setup, the effect of the heat transfer
through external walls of the heated building on the
outdoor temperature sensor can be compensated.
-5.0 ÷ 0.0°C
-2.0