English 31
SPECIAL PARAMETERS
Parameters for oor foundation drying are in the group F1.
Procedures for the F parameters setup is the same as the procedure for the
setup of user and service parameters.
Parameters for oor foundation drying:
Para-
meter
Parameter name Setup range Default
value
F1.1 ACTIVATION OF FLOOR DRYING 0–NO
1–YES
0
F1.2 INTERVAL 1: START TEMPERATURE (°C) 10 ÷ 60°C
20
F1.3 INTERVAL 1: DURATION 1 ÷ 15 days
10
F1.4 INTERVAL 2: START TEMPERATURE (°C) 10 ÷ 60°C
20
F1.5 INTERVAL 2: DURATION 1 ÷ 15 days
5
F1.6 INTERVAL 3: START TEMPERATURE (°C) 10 ÷ 60°C
45
F1.7 INTERVAL 3: DURATION 1 ÷ 15 days
10
F1.8 INTERVAL 4: START TEMPERATURE (°C) 10 ÷ 60°C
45
F1.9 INTERVAL 4: DURATION 1 ÷ 15 days
5
F1.10 INTERVAL 4: END TEMPERATURE (°C) 10 ÷ 60°C
20
Floor foundation drying prole – factory setting:
After the oor foundation drying function is nished, it will automatically switch
o.
days